TU U V.2.7.-26.8-35492904-004:2010 with amendment 4

Rock mineral wool slabs

Product Description:

Fire Protection Slabs for Concrete Lamel are non-combustible, hydrophobized, thermal and sound insulation slabs made of mineral wool based on basalt group rocks.

Can be manufactured with aluminum foil or fiberglass coating.

Application:

In civil and industrial construction, during new construction and reconstruction of buildings and structures for various purposes, as fire protection and thermal insulation for reinforced concrete structures (reinforced concrete columns and floors). The boards are certified as the main element of the concrete fire protection system.

Application instructions:

Installation according to the Fire Protection Work Regulations “SD-FIRE PROTECTION Concrete fire protection system, consisting of mineral wool boards of the “Concrete Fire Protection Boards (MC, AF, SS, SP)” brand and anchoring metal elements (anchor+washer) HILTI IDMS”.

Storage:

Store in covered warehouses, preventing exposure to precipitation. During transportation, protect from damage and moisture.

Transportation:

Transportation must be carried out in accordance with the requirements of DBN G.1-4, DSTU B V.2.7-167. Products are shipped to the consumer no earlier than 24 hours after storage in the warehouse.

Packaging Information:

Polyethylene heat-shrink film is used for packaging.

Main physical and mechanical characteristics:

Parameter

Unit of measurement

Board

Fire protection for concrete lamel

Test Method

Density

kg/m3

70-90

DSTU B V.2.7-38-95

Thermal conductivity, λ25

W/mK

0,037*

DSTU B V.2.7-105-2000

Thermal conductivity, λA

W/mK

0,041**

DSTU B.V.2.7-182:2009

Thermal conductivity, λB

W/mK

0,043**

DSTU B.V.2.7-182:2009

Compressive strength, not less than

kPa

50

DSTU B V.2.7-38-95

Moisture content by mass, not more than

%

0,5

DSTU B V.2.7-38-95

Organic matter content, not more than

%

3

DSTU B V.2.7-38-95

Flammability

degree

NG

DSTU B V.2.7-70-98

 

 

Geometric parameters:

Parameter

Unit of measurement

Value

Test Method

Length

mm

1000 (±2%)

DSTU B V.2.7-38-95

Width

mm

200 (± 1.5%)

DSTU B V.2.7-38-95

Thickness (in 10 mm increments)

mm

60-150 in 10 mm increments (+ 3 mm; – 2 mm)

DSTU B V.2.7-38-95

 

 

 

 


 

TU U V.2.7.-26.8-35492904-004:2010 (Amendment No. 4)

Non-combustible, hydrophobized mineral wool boards

 

Product Description:

Metal Fire Protection Board is a non-combustible, hydrophobized, thermal and sound insulation board made of mineral wool based on basalt group rocks.

Application:

In civil and industrial construction for new construction and reconstruction of buildings and structures of various purposes as thermal insulation and fire protection of metal structures.

To increase the fire resistance limit of load-bearing metal structures with a fire resistance limit from 60 to 180 minutes.

Certified in the metal fire protection system and the air duct fire protection system.

Application instructions:

Installation according to the Fire Protection Work Regulations “SD-FIRE PROTECTION Metal Fire Protection System” for cladding metal structures, consisting of mineral wool boards of the “Metal Fire Protection Boards (MC, AF, SS, SP)” brand and Ceresit CM 17 adhesive”, “SD-FIRE PROTECTION Air Ducts Fire Protection System” for cladding steel air ducts, consisting of mineral wool boards of the “Metal Fire Protection Boards (MC, AF, SS, SP)” brand and Ceresit CM 17 adhesive”.

Storage:

Store in covered warehouses, preventing exposure to precipitation. During transportation, protect from damage and moisture.

Transportation:

Transportation of boards must be carried out in accordance with the requirements of DBN G.1-4, DSTU B V.2.7-167. Products are shipped to the consumer no earlier than 24 hours after storage in the warehouse.

Packaging Information:

Polyethylene heat-shrink film is used for packaging.

Main physical and mechanical characteristics:

Parameter

Unit of measurement

Value

Test Method

Density

kg/m3

165 (±15)

DSTU B V.2.7-38

Thermal conductivity, *λ25

W/mK

0,037

DSTU B V.2.7-105

Thermal conductivity, **λA

W/mK

0,042

DSTU B.V.2.7-182

Thermal conductivity, **ΛB

W/mK

0,045

DSTU B.V.2.7-182

Compressive strength at 10% linear deformation, not less than

kPa

20

DSTU B V.2.7-38

Moisture content by mass, not more than

%

0,5

DSTU B V.2.7-38

Organic matter content, not more than

%

3

DSTU B V.2.7-38

Flammability

degree

NG

DSTU B V.2.7-70

*- according to protocol No. 56K/17;

 


**- according to protocol No. 94K/17.

 

Geometric parameters:

Parameter

Unit of measurement

Value

Length

mm

2400,1200 (±2%)

Width

mm

1000,600 (±1.5%)

Thickness

mm

30-70 in 10 mm increments (+3 mm; -2 mm)


 

TU U V.2.7.-26.8-35492904-004:2010 (Amendment No. 4)

Rock mineral wool slabs

Product Description:

Fire Protection Door Slab is a non-combustible thermal and acoustic insulation slab made from rock mineral wool based on basalt group rocks.

Application:

Fire Protection Door Slabs are specially designed and intended for fire protection insulation of fire-rated doors and gates.

Application instructions:

Installation of slabs in the frame of fire-rated doors and gates as fire protection filler is carried out based on structural features in accordance with the technical documentation of the door and gate manufacturer.

Storage:

Store in covered warehouses, preventing exposure to precipitation. During transportation, protect from damage and moisture.

Transportation:

Transportation must be carried out in accordance with the requirements of DBN G.1-4, DSTU B V.2.7-167. Products are shipped to the consumer no earlier than 24 hours after storage in the warehouse.

Packaging Information:

Polyethylene heat-shrink film is used for packaging.

Main physical and mechanical characteristics:

Parameter

Unit of measurement

Fire Protection Door Slab 110

Fire Protection Door Slab 190

Test Method

Density

kg/m3

100-120

170-200

DSTU B V.2.7-38-95

Thermal conductivity λ25

W/mK

0,037

0,038

DSTU B V.2.7-105-2000

Compressive strength at 10% linear deformation, not less than

kPa

10

20

DSTU B V.2.7-38-95

Moisture content by mass, not more than

%

0,5

0,5

DSTU B V.2.7-38-95

Organic matter content, not more than

%

3,0

3,0

DSTU B V.2.7-38-95

Flammability

degree

NG

NG

DSTU B V.2.7-70-98

 

Geometric parameters:

Parameter

Unit of measurement

Value

Test Method

Length

mm

1000; 1200; 2000; 2400 (±2%)

DSTU B V.2.7-38-95

Width

mm

200, 600; 1000; 1200 (±1.5%)

DSTU B V.2.7-38-95

Thickness (in 10 mm increments)

mm

50-140 in 10 mm increments (+5 mm; -2 mm)*, 30-80 in 10 mm increments (+5 mm; -2 mm)**

DSTU B V.2.7-38-95

 


*-for Fire Protection Door Slab 110;

 


**-for Fire Protection Door Slab 190.

TU U V.2.7.-26.8-35492904-004:2010 (Amendment No. 4)

Rock mineral wool slabs

Product Description:

Concrete Fire Protection Boards are non-combustible, hydrophobized, thermal and sound insulation boards made of mineral wool based on basalt group rocks.

Can be manufactured with aluminum foil or fiberglass coating.

Application:

The boards are intended for use in civil and industrial construction, in new construction and reconstruction of buildings and structures for various purposes as fire protection and thermal insulation of reinforced concrete structures (reinforced concrete columns and floors).

The boards are certified as the main element of the concrete fire protection system.

Application instructions:

Installation according to the Fire Protection Work Regulations “SD-FIRE PROTECTION Concrete fire protection system, consisting of mineral wool boards of the “Concrete Fire Protection Boards (MC, AF, SS, SP)” brand and anchoring metal elements (anchor+washer) HILTI IDMS”.

Storage:

Store in covered warehouses, preventing exposure to precipitation. During transportation, protect from damage and moisture.

Transportation:

Transportation must be carried out in accordance with the requirements of DBN G.1-4, DSTU B V.2.7-167. Products are shipped to the consumer no earlier than 24 hours after storage in the warehouse.

Packaging Information:

Polyethylene heat-shrink film is used for packaging.

Main physical and mechanical characteristics:

Parameter

Unit of measurement

Board

Concrete Fire Protection 80

Test Method

Density

kg/m3

70-90

DSTU B V.2.7-38-95

Thermal conductivity, λ25

W/mK

0,037*

DSTU B V.2.7-105-2000

Thermal conductivity, λA

W/mK

0,038**

DSTU B.V.2.7-182:2009

Thermal conductivity, λB

W/mK

0,040**

DSTU B.V.2.7-182:2009

Compressive strength at 10% linear deformation, not less than

kPa

10

DSTU B V.2.7-38-95

Compressive strength, not less than

kPa

DSTU B V.2.7-38-95

Water absorption during partial immersion, not more than

%

10

DSTU B V.2.7-38-95

Moisture content by mass, not more than

%

0,5

DSTU B V.2.7-38-95

Organic matter content, not more than

%

3

DSTU B V.2.7-38-95

Flammability

degree

NG

DSTU B V.2.7-70-98

*-according to protocol No. 58K/17;

 


**-according to protocol
No. 96K/17.

 

Geometric parameters:

Parameter

Unit of measurement

Value

Test Method

Length

mm

1200 (± 2%)

DSTU B V.2.7-38-95

Width

mm

600 (± 1.5%)

DSTU B V.2.7-38-95

Thickness (in 10 mm increments)

mm

50-150 with 10 mm increments (+ 3 mm; – 2 mm)

DSTU B V.2.7-38-95